Emergency eyewash stations, placement and testing

The emergency eyewash is the one piece of safety equipment that does nothing at all until the worst ten seconds of somebody’s working life, and then everything depends on it. That makes it easy to neglect. I have tested eyewash stations that produced brown water, stations that gave a jet hard enough to hurt, one with a dust cap that had fused in place, and a beautifully installed unit behind a locked door in a corridor nobody used.

None of those failures was about the equipment purchased. All of them were about where it was put and whether anyone checked it.

Why the first seconds decide the outcome

Chemical injury to the eye begins on contact. Acids tend to coagulate surface tissue, which somewhat limits how deep they penetrate. Alkalis are generally worse, because they continue to penetrate the eye and can cause damage that keeps developing after the splash. With either, the most important first aid action is copious irrigation with water or a suitable flushing fluid, started immediately and continued for a long time.

Every delay matters. A person with a chemical in the eye cannot see well, is in pain, and may be panicking. They need to reach the station by feel and memory, open it without searching for a control, and keep their eyes in the flow long enough to do some good. Placement and design should be judged against that scenario, not against a floor plan.

What the standards require

In the United States, OSHA’s first aid rule requires that where the eyes or body of any person may be exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing must be provided within the work area for immediate emergency use. The text is in 29 CFR 1910.151. OSHA does not set detailed performance criteria in that rule, and the consensus standard used to define “suitable” is ANSI/ISEA Z358.1.

The main requirements of ANSI/ISEA Z358.1 for eyewash stations and showers are these.

  • The unit must be reachable within 10 seconds, on the same level as the hazard, along a travel path free of obstructions. The standard’s appendix relates 10 seconds to about 55 feet, or 16.8 metres, but the time and the route are what count.
  • The flushing fluid must be tepid, which the standard defines as between 16 and 38 degrees Celsius, or 60 to 100 degrees Fahrenheit.
  • The unit must provide a continuous flow for at least 15 minutes.
  • An eyewash must deliver at least 1.5 litres per minute, an eye and face wash at least 11.4 litres per minute, and a drench shower at least 75.7 litres per minute.
  • The valve must activate in one second or less and stay open without the use of the operator’s hands, so both hands are free to hold the eyelids open.
  • Where the hazard involves strong acids or caustics, the appendix recommends that the unit be immediately adjacent to the hazard.

Europe uses the EN 15154 series, which covers plumbed safety showers and eyewash units as well as non plumbed self contained units in separate parts. The EU and the UK do not have a prescriptive placement rule equivalent to the 10 second criterion. Instead, the need for eyewash facilities flows from the employer’s risk assessment under national law, such as the COSHH and first aid regulations in the UK. Many European sites adopt the ANSI criteria as a practical benchmark, which is sensible, but it is a choice rather than a legal requirement in most countries.

Placement that works in a real building

The 10 second rule is a minimum, and a floor plan can be misleading. Walk the route yourself with your eyes closed and a colleague guiding you, starting from the actual point of use. You will learn more in a minute than from any drawing.

  • Do not put a door in the path, and certainly not one that locks or opens towards the person.
  • Do not require a change of level. Stairs and ladders are a serious hazard to somebody who cannot see.
  • Keep the area around the unit clear. Pallets, waste bins and hose reels have a way of migrating into the space in front of eyewash stations.
  • Make the location obvious, with a highly visible sign and good lighting, so it can be found by people who have never used it.
  • Protect the supply from freezing outdoors, and from overheating in the sun or in hot plant rooms, where the water in the pipe may be far from tepid.
  • Fit tempered water where needed. Cold water is uncomfortable enough that people stop flushing early, which defeats the purpose.

Battery rooms, chemical stores, laboratories and dosing areas are the obvious locations. Less obvious ones include workshops where cleaning chemicals are decanted, water treatment plants, and maintenance areas where people handle hydraulic fluid or degreasers.

Personal wash bottles are not a substitute

Squeeze bottles of sterile solution are useful for immediate first response and for small particles, and they can be carried to remote areas. The standard treats them as supplementary. They cannot provide 15 minutes of continuous irrigation and must not replace a properly located plumbed or self contained unit where corrosive hazards exist.

Testing and maintenance

Plumbed eyewash stations should be activated weekly. That weekly run checks that the unit works, clears sediment from the supply, and reduces the stagnant water in the pipe where bacteria and amoebae can grow. Run it long enough for the water to run clear. A short burst into a bucket is not a test.

Each unit should also be inspected annually against the full requirements of the standard, including flow rate, temperature, height and the area around it. Self contained units are maintained according to the manufacturer’s instructions, which usually means changing the flushing fluid or preservative at a specified interval and checking that seals and caps are intact.

Keep a record of every test on a tag at the unit and in a central log. The tag tells the person at the unit that it has been checked. The log tells you which units were missed during a busy month. In my experience, the units most often missed are the ones in low traffic areas, which are frequently the ones that serve the most dangerous chemicals.

Train people to use it

A station nobody has tried is a station nobody knows how to use. Let people activate it during training. Show them how to hold their eyelids open, roll their eyes, remove contact lenses during flushing if possible, and keep flushing for the full period even though the pain eases. Make sure someone calls for help and that the injured person gets medical assessment afterwards.

Eyewash is a response to a failure of other controls. Substituting less hazardous chemicals, closed transfer systems, proper splash goggles and good decanting practice all come first. The general background on eyewash provision is simple. Getting the detail right for your site depends on local regulation and a competent risk assessment, and on someone actually walking the route.